Local Mute Control

From exigoWiki
Revision as of 14:03, 20 June 2016 by Gsorensen (talk | contribs)
Jump to navigation Jump to search

Local Mute Control will force any Control Output that is being used (and configured with Local Mute as Source) to trigger. As with other broadcasts, it will be added to the queue if other broadcasts with higher priority are active in the selected zone.

Amplifier -> Control Inputs -> CI -> CI_1-CI_6 -> on_action/off_action

or

Access Panel -> Programmable Keys -> Key -> p1-px -> press_action/release_action

Local Mute Control 1.png


Mute ID The Local Mute to be triggered. This is the source in the control output that directs the actual physical function.

Activation Start, Stop or Toggle the Local Mute.

Destination The zones in which Local Mute will be started. The zone and source must correspond to the function configured in the output.

Priority The priority of the broadcast. The muting will be active as long as the activity in the selected zone has a lower priority than the one set here. For example, the operator wants to mute GA with Priority 20, but he wants to hear the Abandon Alarm with Priority 15. In this case, Priority can be set to 18 here.