Redundancy Funtions

From exigoWiki
Revision as of 15:24, 30 March 2017 by Gsorensen (talk | contribs) (Redundant Controller)
Jump to navigation Jump to search

This article describes different redundancy concepts for PA system in general and for Exigo.

The Exigo system supports several redundancy functions, allowing even a single system to become more redundant.
Depending on different demands that projects may have, there may be a need for one or more redundancy functionality.

Backup Amplifier

This is also refereed to as hot standby amplifier.
The basic concept is that if one amplifier fails, a backup amplifier will take over.
Exigo ENA Amplifiers have inbuilt support for backup amplifier switch-over where one amplifier can be designated as backup for up to six other amplifiers.

Backup Amplifier


This functionality is available from Exigo 1.3 and later.
More information about this feature can be found here.

A-B Wiring

To avoid loosing audio coverage in a area if an amplifier fails, it is possible to design the solution with A-B wiring.
The concept is that you design the speaker layout in a given area (typically a zone) so that the speakers are managed from two different amplifiers.
If one of the amplifiers fails you still have audio in 50% of the speakers.

A-B Wiring


Redundant Controller

The Exigo system controller can also be duplicated (hot standby) to ensure full operation of the system in the event of a faulty system controller.

Redundant (hot standby) Controller


More information about this feature can be found here.

A-B System

A complete A-B system consists of two complete PA systems that work together as one system.
Both systems will have a System Controller and a number of amplifiers.
The A and the B system must be physically separated.
If one of the system fail you will still have audio coverage.

A-B System Principle


More information about this feature can be found here

Redundant Network

All of the Exigo devices have dual Ethernet ports. These can be used for redundancy connection.
There are many ways of designing redundancy networks depending on the projects demands.
With Exigo it is possible to design redundant network even in a single system.
If one of the switches should fail, the system will still be up and running.

Redundant Network solution


This example shows a redundant network in a very small singel Exigo system.

Summary

These examples are the most typical redundancy functionality that is used in PA systems.
It is also possible to combine two or more for even more redundancy.