Difference between revisions of "Volume Controllers"

From exigoWiki
Jump to navigation Jump to search
(Equipment)
Line 9: Line 9:
  
 
== Equipment ==
 
== Equipment ==
Zenitel offers several volume controllers both for single and [[A-B System Principle | A-B systems]].<br>
+
Zenitel offers several volume controllers both for single and [[A-B System Principle | A-B systems]]:<br>
  
 
{| class="wikitable"
 
{| class="wikitable"

Revision as of 13:23, 30 November 2016

Volume Override in Zone 1

This article article describes how to use volume controllers on Exigo.

It is possible to use local volume controllers on Exigo.
During emergency calls the local volume setting must be bypassed.
The volume override uses the 24VDC control output from the ESC1 or the ENA amplifier.
Volume override is activated when the 24VDC disappears.

Equipment

Zenitel offers several volume controllers both for single and A-B systems:

Item no: Short code: Description:
300 5010 210 VM15-R Volume Control 4 Wire Override 15W Single PA System
300 5010 213 VM50-R Volume Control 4 Wire Override 50W Single PA System
300 5010 211 VM15-RD Dual Volume Control 4 Wire Override 2x15W
300 5010 214 VM50-RD Dual Volume Control 4 Wire Override 2x50W

Configuration

Wiring