EN 54

From exigoWiki
Revision as of 09:29, 29 November 2016 by Gsorensen (talk | contribs) (Surge Protection - 230VAC)
Jump to navigation Jump to search
EN54 label

This article describes the different precautions that needs to be considered when using Exigo where EN 54 is applicable.
Exigo is tested and certified according to EN54-16: Fire detection and fire alarm systems.
In order to comply with the strict rules of EN54 there are some additional equipment needed:

Item no: Short code: Description:
102 3598 000 Exigo Overvoltage Protection 2x 100V/70V lines (1 per ENA2200)
102 3598 100 Exigo Overvoltage Protection 3x I/O lines
N/A Bourns 1250-2S-230 (surge protection - 230VAC)
N/A Bourns 1320-S-48 (surge protection - 48VDC)
300 5010 176 SPA-REL-V2 Multipurpose potential free relay contact

Exigo Overvoltage Protection 2x 100V/70V lines

In order to comply with the strict rules of EN54 it is mandatory to use overvoltage protection on the speaker lines.

Overvoltage Protection Speaker Line


The diagram shows how the overvoltage protection (F21) is wired.

Exigo Overvoltage Protection 3x I/O lines

In order to comply with the strict rules of EN54 it is mandatory to use overvoltage protection when interfacing with external system using the control input(s).

Overvoltage Protection Control Inputs


The diagram show an example on overvoltage protection (F20) on the control inputs:

  • Control inputs 1 and 2 are local buttons located inside the rack. These do not need protections since they are not interfacing to any external system.
  • Control inputs 3, 4 and 5 are interface to the fire alarm system. They need to have overvoltage protection since they are interfacing external systems.

Surge Protection - 230VAC

In order to comply with the strict rules of EN54 it is mandatory to use surge protection on the 230VAC.

Overvoltage Protection Control Inputs


The diagram shows an example on how to wire the surge protection (F10).

Documentation

All manuals for Exigo can be found here.
Manuals/Certification related to EN 54: