Difference between revisions of "Control Inputs"

From exigoWiki
Jump to navigation Jump to search
(Control Inputs - Monitoring)
Line 13: Line 13:
 
** Live Speech from external microphone
 
** Live Speech from external microphone
  
==Control Inputs - Connections==
+
== Control Inputs - Connections ==
 
'''Connections on rack devises'''
 
'''Connections on rack devises'''
 
[[File:Control Inputs 2.JPG|thumb|left|700px|Rack devices]]
 
[[File:Control Inputs 2.JPG|thumb|left|700px|Rack devices]]
Line 22: Line 22:
 
<br style="clear:both;" />
 
<br style="clear:both;" />
  
==Configuration==
+
== Configuration ==
 
Configuration of Control Inputs are done in EMT:
 
Configuration of Control Inputs are done in EMT:
 
[[File:Control Inputs 4.JPG|thumb|left|700px|Input 1 on amplifier starts «Fire Alarm» message in «Main Building»]]
 
[[File:Control Inputs 4.JPG|thumb|left|700px|Input 1 on amplifier starts «Fire Alarm» message in «Main Building»]]
Line 32: Line 32:
 
* Set relevant parameters in the dialog box that appears
 
* Set relevant parameters in the dialog box that appears
  
==Control Inputs - Monitoring==
+
== Control Inputs - Monitoring ==
 
[[File:Control_Inputs_5.jpg|thumb|left|700px|Control Input]]
 
[[File:Control_Inputs_5.jpg|thumb|left|700px|Control Input]]
 
<br style="clear:both;" />
 
<br style="clear:both;" />
Line 54: Line 54:
 
[[File:Control Inputs 7.JPG|thumb|left|650px|EMT - enable monitoring]]
 
[[File:Control Inputs 7.JPG|thumb|left|650px|EMT - enable monitoring]]
 
<br style="clear:both;" />
 
<br style="clear:both;" />
 +
 +
== Parallel Wired Inputs ==
 +
In an A-B system, it is required that signals from external systems such as fire detection are routed to both the A and B systems.
 +
 +
=== Connection with Dual-Pole Switch ===
 +
If the external system has two physical outputs, a dual-pole switch connection must be made between Exigo and the external system as shown below:
 +
[[File:Control Inputs 8.JPG|thumb|left|650px|A - B Dual-Pole Switch Wiring]]
 +
<br style="clear:both;" />
 +
  
  

Revision as of 11:44, 21 September 2016

Devices with Control Inputs available

This article describes the control inputs on Exigo in general.

  • Control Inputs are available on:
    • System Controller
    • Amplifiers
    • Access Panels (Not EX panels)
  • 6 inputs on each device
  • Inputs are used e.g. for triggering:
    • General Alarm
    • Fire Alarm
    • Live Speech from external microphone

Control Inputs - Connections

Connections on rack devises

Rack devices


Connections on access panels

Rack devices


Configuration

Configuration of Control Inputs are done in EMT:

Input 1 on amplifier starts «Fire Alarm» message in «Main Building»


  • In Components view open Input Actions
  • In System, identify the device and expand to Control Inputs
  • Drag the desired Input Action to the on_action or the off_action
  • Set relevant parameters in the dialog box that appears

Control Inputs - Monitoring

Control Input


  • Conventional inputs have two states:
    • Contact is Open, or
    • Contact is Closed

This makes the control input vulnerable - cable break is not detected.
On System Controller and Amplifiers it is possible to monitor the control inputs. Access panels do not support monitoring.
This is done by connecting two resistors as close as possible to the external switch/relay, one in series and one in parallell.

Control Input - Monitored


The resistor connected in series with the external switch/relay shall have a value of 1 kΩ, while the resistor connected in parallel shall be 2.2 kΩ.

Monitored Inputs have four states:

  • Contact is Open, or
  • Contact is Closed
  • Short circuit (error)
  • Open circuit (error)

Monitoring of inputs must be enabled in EMT:

EMT - enable monitoring


Parallel Wired Inputs

In an A-B system, it is required that signals from external systems such as fire detection are routed to both the A and B systems.

Connection with Dual-Pole Switch

If the external system has two physical outputs, a dual-pole switch connection must be made between Exigo and the external system as shown below:

A - B Dual-Pole Switch Wiring