Configuration of distribution of General Alarm and high priority live speech from Exigo to AlphaCom

From exigoWiki
Revision as of 12:41, 6 April 2017 by Gsorensen (talk | contribs) (AlphaPro)
Jump to navigation Jump to search

This article describes the configuration needed when distributing General Alarm and high priority live speech from Exigo to AlphaCom/ACM.

  • It is important that users of AlphaCom/ACM are not able to disconnect the Exigo PA call from the InterCom station.
  • All audio from Exigo to AlphaCom/ACM will be distributed with handset and volume override.

Configuration Example

Group number, Program Number, Directory Number and Class Of Service can of cause be changed to user request.

EMT

Configuration in Exigo Management Toll (EMT):

  • Drag AlphaCom Feature to System -> Integration -> AlphaCom
AlphaCom Feature


  • Drag the configured AlphaCom Feature to the designated zone
AlphaCom Feature


AlphaPro

Overview of configuration in AlphaPro:

AlphaCom Description Info
Station group used in AlphaCom to include stations receiving EXIGO calls Group 10 NB! The group feature/directory number is not used. Only the list of group members
Audio Program Channel used for audio distribution Audio Program 7
Flags set: Program over Conversation, Volume/Handset Override
NB! The program feature/directory number is not used.
NB! The program channel must not be related to physical hardware. (AGA/APC)
Feature for triggering audio to ACM stations inn group 10 "8075" "Exigo Call"
Feature 118, ID = 7 , Parameter 2 = 10
Will start Program 7 to all members of Group 10
Event handler for inhibit program selection during Exigo call.
This will deactivate dialing "800" for canceling program during PAGA.
Event Type: 15 - Event Trigger Feature
Sub Event: 10
When Change To: ON
When Related To: Directory Number
ID: 8075

Action:
$MCC U1 U5 U0
$MCC U2 U5 U0
$MCC U3 U5 U0
$MCC U4 U5 U0
$MCC U5 U5 U0
$MCC U16 U5 U0
Removes 5 - Audio Program Selection from Class Of Service 1,2,3,4,5 and 16
Should be adjusted to reflect the Class Of Service actually used in the system.
Event handler trigger for enabling program selection again after Exigo call Event Type: 15 - Event Trigger Feature
Sub Event: 10
When Change To: OFF
When Related To: Directory Number
ID: 8075

Action:
$MCC U1 U5 U1
$MCC U2 U5 U1
$MCC U3 U5 U1
$MCC U4 U5 U1
$MCC U5 U5 U1
$MCC U16 U5 U1
Add 5 - Audio Program Selection to Class Of Service 1,2,3,4,5 and 16
Should be adjusted to reflect the Class Of Service actually used in the system.
Add feature 118 "Program Source" to Class Of Service 15 (Outside telephone)


  • Configuration of Station Group
AlphaCom - Group configuration


  • Configuration of Audio Program
AlphaCom - Audio Program configuration


  • Configuration of Directory Numbers/Features
AlphaCom - Directory Numbers/Features configuration


  • Configuration of Events
AlphaCom - Events configuration


  • Configuration of Class Of Service
AlphaCom - Class Of Service configuration


Availability

This function is available from Exigo 1.3 and newer.