Local mute is a common PA function where one or more speakers are disconnected when a specific access panel is used. This is commonly used when there are a high probablity of feedback.

Wiring example

See Wiring Local mute

Configuration

In Exigo a Audio activity or a Local mute output function needs to be configured on the relevant control output

Local mute output action

Local mute configured for one access panel In the local mute output function only the access panel and zone needs to be set. With the settings shown here the local mute will only trigger the control output when "ECPIR-3P A1" sends live speech to Zone 1.


Audio activity

Audio activity configured for local mute Image shows how Control output 1 should trigger when "ECPIR-3P A1" is used in Zone 1. This implies that the access panel is placed in an area covered by zone 1. If the access panel sends Live speech into zone 1 the function will trigger, but if it sends the live speech to any other zone it will not trigger. Other activity, such as message control or similar will not trigger this activity as the source must be the access panel itself.