Difference between revisions of "Fault Indication"
(→Assigning Fault Indication to a Control Output) |
(→Parameter details) |
||
Line 36: | Line 36: | ||
'''Delay Activation:''' Delays control output activation for the stipulated number of seconds when triggered. | '''Delay Activation:''' Delays control output activation for the stipulated number of seconds when triggered. | ||
− | |||
− | |||
'''Subscribe To:''' Options are Faults or Warnings. | '''Subscribe To:''' Options are Faults or Warnings. | ||
− | + | '''Filter Script:''' Her you paste/type in the script you need. | |
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | ===Advanced Options:=== | + | === Advanced Options: === |
::'''Limit High Not OK:''' When the Control Output is cleared, and feedback voltage is at or above this value, the output is considered fed with alien voltage. | ::'''Limit High Not OK:''' When the Control Output is cleared, and feedback voltage is at or above this value, the output is considered fed with alien voltage. | ||
Revision as of 12:16, 9 September 2016
Control Outputs are configured by defining one or more actions to be triggered on an output event.
The Fault Indication function is used to trigger the control output on defined fault indication.
This can be used to send a signal to external systems (like BMG (Building Management Systems). It can also be used to give visual notifications when there is fault in the system.
Contents
Assigning Fault Indication to a Control Output
To assign the function Fault Indication to an Control Output:
- In Components view, open Output Actions
- In System, identify the Controller, the Amplifier or the Access Panel to be used, and expand to Device > Control Outputs.
- Drag Fault Indication to the Control Output you want to use.
Configuration
Visual indication of a fault in the system
The output is used to give a visual indication of a an error in Zone 4.
- Drag Fault Indication to the desired Control Output.
- Select Zones in Filter Mode. This will give you the option to select zones.
- Select Zone 4 in Affected Zones.
- In Severity (level) select Error.
In this example an error in Zone 4 will trig Control Output 1.
Parameter details
Idle State: Sets the idle state for the output. The options are Normally Open or Normally Closed
Delay Activation: Delays control output activation for the stipulated number of seconds when triggered.
Subscribe To: Options are Faults or Warnings.
Filter Script: Her you paste/type in the script you need.
Advanced Options:
- Limit High Not OK: When the Control Output is cleared, and feedback voltage is at or above this value, the output is considered fed with alien voltage.
- Limit Low OK: When the Control Output is set, and feedback voltage is above this value, the output is considered active OK.