==Parameter details==
 
==Parameter details==
 +
'''Idle State:''' Sets the idle state for the output. The options are Normally Open or Normally Closed
  
 +
'''Delay Activation:''' Delays control output activation for the stipulated number of seconds when triggered.
 +
 +
'''Reporting System:''' The system, i.e. System A, System B or System A and B, from which faults will be received (only available in A-B System projects).
 +
 +
'''Subscribe To:''' Options are Faults or Warnings.
 +
 +
===Filter Parameters:===
 +
::'''Affected Devices:''' Trigger on faults that affect selected devices.
 +
 +
::'''Affected Zones:''' Trigger on faults that affect selected zones.
 +
 +
::'''Affected Lines:''' Trigger on faults that affect selected audio lines.
 +
 +
::'''Severity:''' Trigger on faults at selected levels.
 +
 +
::'''Fault State:''' Trigger on faults in selected state.
 +
 +
::'''System Message:''' Trigger on faults that have selected messages.
  
 
===Advanced Options:===
 
===Advanced Options:===

Revision as of 12:26, 10 August 2016

Visual indication of Audio Activity

Control Outputs are configured by defining one or more actions to be triggered on an output event.

The Fault Indication functions is used to trig a control output when there is fault(s) in the system.

This can be used to send a signal to external systems (like BMG (Building Management Systems). It can also be used to give visual notifications when there is fault in the system.

Assigning Fault Indication to a Control Output

Configuration

Visual indication of a fault in the system

Parameter details

Idle State: Sets the idle state for the output. The options are Normally Open or Normally Closed

Delay Activation: Delays control output activation for the stipulated number of seconds when triggered.

Reporting System: The system, i.e. System A, System B or System A and B, from which faults will be received (only available in A-B System projects).

Subscribe To: Options are Faults or Warnings.

Filter Parameters:

Affected Devices: Trigger on faults that affect selected devices.
Affected Zones: Trigger on faults that affect selected zones.
Affected Lines: Trigger on faults that affect selected audio lines.
Severity: Trigger on faults at selected levels.
Fault State: Trigger on faults in selected state.
System Message: Trigger on faults that have selected messages.

Advanced Options: