Line 50: Line 50:
 
::'''Limit High Not OK:''' When the Control Output is cleared, and feedback voltage is at or above this value, the output is considered fed with alien voltage.
 
::'''Limit High Not OK:''' When the Control Output is cleared, and feedback voltage is at or above this value, the output is considered fed with alien voltage.
 
::'''Limit Low OK:''' When the Control Output is set, and feedback voltage is above this value, the output is considered active OK.
 
::'''Limit Low OK:''' When the Control Output is set, and feedback voltage is above this value, the output is considered active OK.
 +
::'''On Lost Connection:''' Fall back to this state on lost connection with ESC. Available Settings: '''Idle State, No Change, Open, Closed'''.
 +
  
 
  {{Note}} To avoid errors one fault indication should not mix Zones and Channels.
 
  {{Note}} To avoid errors one fault indication should not mix Zones and Channels.

Revision as of 14:54, 16 April 2018

Visual indication of faults in the system

The Fault Indication function is used to trigger the control output on faults or warnings in the system.

This can be used to send a signal to external systems such as BMS (Building Management Systems)). It can also be used to provide visual notifications when there is fault in the system.

Assigning Fault Indication to a Control Output

To assign the function Fault Indication to an Control Output:

  1. In Components view, open Output Actions
  2. In System, identify the Controller, the Amplifier or the Access Panel to be used, and expand to Device > Control Outputs.
  3. Drag Fault Indication to the Control Output you want to use.
Assigning Fault Indication function to a Control Output


Configuration

Visual Indication of a Fault in the System

In this example, the output is used to give a visual indication of an error in Zone 4.

  1. Under Output Actions, drag Fault Indication to the desired Control Output
  2. Select Zones in Filter Mode. This will give you the option to select zones
  3. Select Zone 4 in Affected Zones
  4. In Severity (level) select Error
Visual indication of errors in Zone 4


In this example, an error in Zone 4 will trigger Control Output 1.

Parameter Details

Idle State: Sets the idle state for the output. The options are Normally Open or Normally Closed.

Delay Activation: Delays control output activation for the stipulated number of seconds when triggered.

Faults in System: The system, i.e. System A, System B, or System A and B, from which faults will be received (only available in A-B System projects).

Subscribe To: Options are Faults or Warnings.

Filter Parameters:

Filter Mode: Trigger on faults that affect selected System Messages, Zones, Devices.
Severity (level): Trigger on faults at selected levels. Options are: Emergency, Alert, Critical, Error.
Fault State: Trigger on faults in selected state. Options are: Any, Active.
System Message: Trigger on faults that have selected messages.

Filter Script

Filter Script field will show the actual script which will be used to determine if output should be triggered or not. This script is constructed based on the selection of filter parameters.

Advanced Options:

Limit High Not OK: When the Control Output is cleared, and feedback voltage is at or above this value, the output is considered fed with alien voltage.
Limit Low OK: When the Control Output is set, and feedback voltage is above this value, the output is considered active OK.
On Lost Connection: Fall back to this state on lost connection with ESC. Available Settings: Idle State, No Change, Open, Closed.


Note.PNG To avoid errors one fault indication should not mix Zones and Channels.

Example of Use:

Case 1: System Messages

The system should trigger a control output connected to another system if any device is missing. Fault indication will in this example be configured as:

  • Filter Mode: System Messages
  • System Message: Missing device

Case 2: Zones

The system should trigger a control output connected to another system if there is a fault which affects Zone 2.
Fault indication will in this example be configured as:

  • Filter Mode: Zones
  • Affected Zones: Zone 2

Case 3: Custom Fault

The system should trigger a control output connected to another system if one of the external faults are triggered . Fault indication will in this example be configured as:

  • Filter Mode: System Messages
  • System Message: External fault

This will trigger on any external fault in the system. If more granularity is required then Filter Mode = Devices can be used to only trigger on external faults from a specific device.