Start alarm from AlphaCom in Exigo A-B system
Jump to navigation
Jump to search
This article explains how to start alarm from AlphaCom on a Exigo A-B system.
Guide on how to set up the redundant AlphaCom integration can be found here.
Starting an alarm from AlphaCom to a redundant Exigo system is done by starting a group call in AlphaCom that starts the Alarm generator in both Exigo A and B controller.
AlphaPro Configuration
- Set up the redundant AlphaCom integration following this guide.
- Set up 2 different DirNo numbers (for example 98001 and 98002) as SIP stations related to PSC A and PSC B trunk:
98001 Setup:
Notice the related to trunk.
98002 Setup:
Notice the related to trunk.
- Make a group and add both dir numbers (98001 and 98002) to the group to be able to call both at the same time from a station:
- Add both dir numbers (98001 and 98002) to the group:
- Now program a DAK to call that group – in this case dir 85 – and this will start the alarm in both Exigo A and B.
EMT Configuration
- Configure 2 identical Action Calls with different directory numbers (for example 98001 and 98002).