Control Outputs are configured by defining one or more actions to be triggered on an output event.
+
The Follow Any Alarm Tone function is used to trigger the control output to follow one, many or any Alarm Tone in one specific zone. It differs from the [[Follow_One_Alarm_Tone|follow one alarm]] in that it can only follow alarms in one zone.
 
 
The Follow Any Alarm Tone function is used to trigger the control output to follow one, many or any Alarm Tone in one specific zone.  
 
  
 
This function can be useful to give visual indication in noisy areas.
 
This function can be useful to give visual indication in noisy areas.
Line 45: Line 43:
 
::'''Limit Low OK:''' When the Control Output is set, and feedback voltage is above this value, the output is considered active OK.
 
::'''Limit Low OK:''' When the Control Output is set, and feedback voltage is above this value, the output is considered active OK.
  
 +
==Example of use:==
 +
It is common in noisy areas to add flashing lights or beacons which will indicate when there are activity on the PA. The "follow any alarm" function can in this case be used to pulse the flashing light in the same pattern as a any alarm sent to the zone. The configuration will then have:<br>
 +
Source: None<br>
 +
Destination: "Noisy zone 1", "Noisy zone 2"<br>
 +
Priority range: 1-40<br>
 +
Follow alarm tone: checked<br>
 +
With this setup the control output will trigger in the same pattern as any alarm tone sent to the zone. For a general alarm (7 short burst, one long burst) the people in the area will then see the type of alarm which is active.
  
  
 
[[Category:Exigo features]]
 
[[Category:Exigo features]]
 
[[Category:Output Actions]]
 
[[Category:Output Actions]]

Revision as of 16:52, 21 November 2016

The control output follows the alarm tone in Zone 1

The Follow Any Alarm Tone function is used to trigger the control output to follow one, many or any Alarm Tone in one specific zone. It differs from the follow one alarm in that it can only follow alarms in one zone.

This function can be useful to give visual indication in noisy areas.


Assigning Follow Any Alarm Tone to a Control Output

To assign the function Follow Any Alarm Tone to an Control Output:

  1. In Components view, open Output Actions
  2. In System, identify the Controller, the Amplifier or the Access Panel to be used, and expand to Device > Control Outputs.
  3. Drag Follow Any Alarm Tone to the Control Output you want to use.
Assigning Follow Any Alarm Tone function to a Control Output


Configuration

Follow alarm tone in Zone 1

  1. Drag Follow Any Alarm Tone to the desired Control Output.
  2. Select the desired Alarm (or Any) in Source.
  3. Select Zone 1 in Zone.
The specified alarm tone in Zone 1 will trig the Control Output 1


In this example the General Alarm (Ship) in Zone 1 will trig Control Output 1.

Parameter details

Idle State: Sets the idle state for the output. The options are Normally Open or Normally Closed

Source: The source that will trigger the alarm output. If Source is not specified, it will be ignored when checking whether the conditions for the audio activity triggering are present or not.

Zone: The zones in which the output on an activity is triggered. If Zone is not specified, it will be ignored when checking whether the conditions for the audio activity triggering are present or not. Note that only one zone can be specified.

Priority Range: The priority range within which the activity is triggered.

Advanced Options:

Limit High Not OK: When the Control Output is cleared, and feedback voltage is at or above this value, the output is considered fed with alien voltage.
Limit Low OK: When the Control Output is set, and feedback voltage is above this value, the output is considered active OK.

Example of use:

It is common in noisy areas to add flashing lights or beacons which will indicate when there are activity on the PA. The "follow any alarm" function can in this case be used to pulse the flashing light in the same pattern as a any alarm sent to the zone. The configuration will then have:
Source: None
Destination: "Noisy zone 1", "Noisy zone 2"
Priority range: 1-40
Follow alarm tone: checked
With this setup the control output will trigger in the same pattern as any alarm tone sent to the zone. For a general alarm (7 short burst, one long burst) the people in the area will then see the type of alarm which is active.