Setting up a small A-B system
This article will explain how to setup and configure a small Exigo A-B system.
System A will have one ESC1 Controller and two ENA2200 Amplifiers.
System B will have one ESC1 Controller and two ENA2200 Amplifiers.
In addition there will be one ECPR-3P connected to the system.
The system will be programmed with 4 Zones.
With the PPT button we will configure Live Speech on all zones.
Before you start configure make sure that all devices have been updated to the latest software/firmware.
Step 1: IP address
Each device will need to be configured with an IP address and subnet which is in range of the AMC-IP card.
Table below lists IP range for a small system with one amplifier and on access panel. All subnets are set to 255.255.255.0
Device | IP | Directory number |
---|---|---|
PSC System A | 10.5.11.11 | |
ESC-1 System A | 10.5.11.100 | 013010 |
ENA 1 System A | 10.5.11.110 | 012010 |
ENA 2 System A | 10.5.11.120 | 012020 |
PSC System B | 10.5.12.11 | |
ESC-1 System B | 10.5.12.100 | 023010 |
ENA 1 System B | 10.5.12.110 | 022010 |
ENA 2 System B | 10.5.12.120 | 022020 |
ECPIR-3P | 10.5.11.200 | 011010 |
Step 2: Primary System Controller Setup
Open up the front of the ESC1 System Controller. Connect your computer to eth0.
- Open a web browser and enter the default IP address of port npe_eth0: 169.254.1.5
- Log in with username: admin and password: alphaadmin
- Select System Configuration > Interfaces
- Enter the appropriate IP address (10.5.11.11 for System A and 10.5.12.11 for System B) in the npe_eth1 field.
This must be done for the ESC System controller for both System A and B.