SNMP recommended parameters

From exigoWiki
Revision as of 09:21, 13 June 2019 by Gsorensen (talk | contribs)
Jump to navigation Jump to search

This article describes the SNMP parameters that are recommended to monitor.


Exigo 1.2.3.13

Exigo 1.2.3.13 is using SNMPv1.

OID Logical name Frequency Unit Priority Description
Memory usage MIB2 Memory usage Once every 60 second All
1.3.6.1.4.1.26122.3.1.4 infoAmplifierType During startup All The device Amplifier Type
1.3.6.1.4.1.26122.3.1.1 infoPackageVersion During startup All The device Package Version
1.3.6.1.4.1.26122.3.2 temp
1.3.6.1.4.1.26122.3.2.1 tempTableCount Number of Temperature entries in tempTable
1.3.6.1.4.1.26122.3.2.2.1.2 tempSensorName During startup SSC + ENA The name of the temperature sensor we are reading
1.3.6.1.4.1.26122.3.2.2.1.7 tempAverageString During startup SSC + ENA The average temperature
1.3.6.1.4.1.26122.3.2.2.1.8 tempAverageValue Twice every 60 second SSC + ENA The average temperature of this sensor in the device
1.3.6.1.4.1.26122.3.3 fan
1.3.6.1.4.1.26122.3.3.1 fanTableCount During startup SSC + ENA Number of Fan entries in fanTable
1.3.6.1.4.1.26122.3.3.2.1.2 fanString During startup SSC + ENA The name of the fan sensor we are reading
1.3.6.1.4.1.26122.3.3.2.1.3 fanValue Once every 60 second SSC + ENA The rotation speed of the fan in RPM
1.3.6.1.4.1.26122.3.7 ampChannel
1.3.6.1.4.1.26122.3.7.1 ampChannelCount During startup ENA The total number of Amplifier channels
1.3.6.1.4.1.26122.3.7.3.1.2 ampChannelString During startup ENA The name of the Amplifier channel
1.3.6.1.4.1.26122.3.7.3.1.3 ampChannelStatus: unknown(1), notOperative(2), channelOk(3), channelFail(4), channelShutdown(5), channelGracefulDegradation(6) Once every 60 second ENA High The Amplifier Channel status
1.3.6.1.4.1.26122.3.6 lineIn Panels
1.3.6.1.4.1.26122.3.6.1.1.5 lineInStatus: unknown(1), lineInOk(2), lineInFail(3), microphoneUnknown(4), microphoneConnected(5), microphoneDisconnected(6), microphoneShorted(7) Once every 60 second Panels High The Line In or Microphone status
1.3.6.1.4.1.26122.3.9 controlInput
1.3.6.1.4.1.26122.3.9.1 controlInputCount During startup ESC + ENA Number of Control Input entries in controlInputTable
1.3.6.1.4.1.26122.3.9.2.1.2 controlInputString During startup ESC + ENA The name of the Control Input
1.3.6.1.4.1.26122.3.9.2.1.3 controlInputStatus: unknown(1), open(2), closed(3), failShorted(4), failOpen(5) Once every 60 second ESC + ENA High The Control Input status
1.3.6.1.4.1.26122.3.10 controlOutput
1.3.6.1.4.1.26122.3.10.1 controlOutputCount During startup ESC + ENA Number of Control Output entries in controlOutputTable
1.3.6.1.4.1.26122.3.10.2.1.2 controlOutputString During startup ESC + ENA The name of the Control Output
1.3.6.1.4.1.26122.3.10.2.1.3 controlOutputStatus: unknown(1), notActive(2), active(3), failNotActive(4), failActive(5) Once every 60 second ESC + ENA The Control Output status