Line 4: | Line 4: | ||
==Downgrade 1.3 to 1.2== | ==Downgrade 1.3 to 1.2== | ||
+ | Recommended downgrade procedure: | ||
+ | # Flash AMC-IP with BSP version 11 | ||
+ | # Install 1.2 Alphasys/BSP | ||
+ | # Clean and factory default AMC-IP | ||
+ | # Build new database in 1.2 version of EMT | ||
+ | # Upload the database with all endpoints | ||
+ | # Install 1.2 on endpoints from AlphaWeb | ||
+ | |||
===Prerequisites=== | ===Prerequisites=== | ||
# Download and install the VS-AlphaCComXEImageUpgrade | # Download and install the VS-AlphaCComXEImageUpgrade | ||
Line 33: | Line 41: | ||
===Turbine devices=== | ===Turbine devices=== | ||
− | * If the system is going to be powered and connected during the downgrade process, it is important that AMC-IP is downgraded before downgrading the turbine-devices. If not, the turbine devices can download a 1.3 database from AMC-IP while running on 1.2 software. This may send the turbine device into a "reboot-loop". If this happens, the station needs to be flashed with production-software. | + | * If the system is going to be powered and connected during the downgrade process, it is important that AMC-IP is downgraded before downgrading the turbine-devices. If not, the turbine devices can download a 1.3 database from AMC-IP while running on 1.2 software. This may send the turbine device into a "reboot-loop". If this happens, the station needs to be flashed with production-software. |
− | |||
− | |||
− |
Revision as of 13:57, 14 March 2017
This article describes how to downgrade an Exigo system between major releases.
Downgrade 1.3 to 1.2
Recommended downgrade procedure:
- Flash AMC-IP with BSP version 11
- Install 1.2 Alphasys/BSP
- Clean and factory default AMC-IP
- Build new database in 1.2 version of EMT
- Upload the database with all endpoints
- Install 1.2 on endpoints from AlphaWeb
Prerequisites
- Download and install the VS-AlphaCComXEImageUpgrade
- Download the latest 1.2 software package
AMC-IP
- Open the VS-AlphaCComXEImageUpgrade and select "Select Image File".
- Navigate to "... Vingtor Stentofon\VS-Tools\AlphaComImages"
- Select "axeu_b3001_a1101303.aimg"
- If server status says: "Could not start HTTP server", a TFTP-server is needed to transfer the image to the AMC-IP.
- Load a tftp-server and set the root folder to:"... \Vingtor Stentofon\VS-Tools\HttpFileServerRoot".
- Write the IP of the AMC-IP that will be flashed --> Connect to target
- If the status window shows: "Bootloader Status Recived - Status OK", everything is ready --> Press "Start Image Upgrade"
When the progress bar is at 100%, navigate to AlphaWeb and verify that versions are:
- Alphasys: 11.1.3.3
- BSP: 31.01
- IPORTANT NOTE: The flashing procedure does not clear the old database, so after performing the flash, it is required to perform a "Clean adn factory default" from alphaweb.
- 1.2 BSP and Alphasys can now be installed from the web upgrade form
Turbine devices
- If the system is going to be powered and connected during the downgrade process, it is important that AMC-IP is downgraded before downgrading the turbine-devices. If not, the turbine devices can download a 1.3 database from AMC-IP while running on 1.2 software. This may send the turbine device into a "reboot-loop". If this happens, the station needs to be flashed with production-software.