Difference between revisions of "SNMP recommended parameters"

From exigoWiki
Jump to navigation Jump to search
(Exigo 1.2.3.13)
 
(42 intermediate revisions by the same user not shown)
Line 6: Line 6:
  
 
{| border="1"
 
{| border="1"
! style="background:#ffd400;" width="200" |OID
+
! style="background:#ffd400;" width="180" |OID
! style="background:#ffd400;" width="150" |Logical name
+
! style="background:#ffd400;" width="980" |Logical name
 
! style="background:#ffd400;" width="150" |Frequency
 
! style="background:#ffd400;" width="150" |Frequency
 
! style="background:#ffd400;" width="80" |Unit
 
! style="background:#ffd400;" width="80" |Unit
! style="background:#ffd400;" width="80" |Priority
+
! style="background:#ffd400;" width="70" |Priority
 +
! style="background:#ffd400;" width="350" |Description
 
|-
 
|-
| Memory usage MIB2 || Memory usage || Once every 60 second || All ||  |
+
| 1.3.6.1.4.1.26122.3.1.4 || infoAmplifierType || During startup || All ||  || The device Amplifier Type
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.1.4 || infoAmplifierType || During startup || All ||  |
+
| 1.3.6.1.4.1.26122.3.1.1 || infoPackageVersion || During startup || All || ||  The device Package Version
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.1.1 || infoPackageVersion || During startup || All ||  |
+
| 1.3.6.1.4.1.26122.3.2 || '''temp''' || || ||  ||
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.2 || '''temp''' ||  ||  ||  |
+
| 1.3.6.1.4.1.26122.3.2.1 || tempTableCount ||  ||  ||  || Number of Temperature entries in tempTable
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.2.1 || tempTableCount || || ||  |
+
| 1.3.6.1.4.1.26122.3.2.2.1.2 || tempSensorName || During startup || SSC + ENA ||  || The name of the temperature sensor we are reading
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.2.2.1.2 || tempSensorName || During startup || SSC + ENA ||  |
+
| 1.3.6.1.4.1.26122.3.2.2.1.7 || tempAverageString || During startup || SSC + ENA ||  || The average temperature
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.2.2.1.7 || tempAverageString || During startup || SSC + ENA ||  |
+
| 1.3.6.1.4.1.26122.3.2.2.1.8 || tempAverageValue || Twice every 60 second || SSC + ENA ||  || The average temperature of this sensor in the device
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.2.2.1.8 || tempAverageValue || Twice every 60 second || SSC + ENA ||  |
+
| 1.3.6.1.4.1.26122.3.3 || '''fan''' || || ||  ||
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.3 || '''fan''' || || ||  |
+
| 1.3.6.1.4.1.26122.3.3.1 || fanTableCount || During startup || SSC + ENA ||  || Number of Fan entries in fanTable
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.3.1 || fanTableCount || During startup || SSC + ENA ||  |
+
| 1.3.6.1.4.1.26122.3.3.2.1.2 || fanString || During startup || SSC + ENA ||  || The name of the fan sensor we are reading
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.3.2.1.2 || fanString || During startup || SSC + ENA ||  |
+
| 1.3.6.1.4.1.26122.3.3.2.1.3 || fanValue || Once every 60 second || SSC + ENA ||  || The rotation speed of the fan in RPM
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.3.2.1.3 || fanValue || Once every 60 second || SSC + ENA ||  |
+
| 1.3.6.1.4.1.26122.3.7 || '''ampChannel''' || || ||  ||
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.7 || '''ampChannel''' || || ||  |
+
| 1.3.6.1.4.1.26122.3.7.1 || ampChannelCount || During startup || ENA ||  || The total number of Amplifier channels
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.7.1 || ampChannelCount || During startup || ENA ||  |
+
| 1.3.6.1.4.1.26122.3.7.3.1.2 || ampChannelString || During startup || ENA ||  || The name of the Amplifier channel
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.7.3.1.2 || ampChannelString || During startup || ENA || |
+
| 1.3.6.1.4.1.26122.3.7.3.1.3 || ampChannelStatus: unknown(1), notOperative(2), channelOk(3), channelFail(4), channelShutdown(5), channelGracefulDegradation(6)|| Once every 60 second || ENA || High || The Amplifier Channel status
 
|-
 
|-
| 1.3.6.1.4.1.26122.3.7.3.1.3 || ampChannelStatus || Once every 60 second || ENA || High |
+
| 1.3.6.1.4.1.26122.3.6 || '''lineIn''' || || Panels || ||
 
|-
 
|-
| || unknown(1) || || || |
+
| 1.3.6.1.4.1.26122.3.6.1.1.5 || lineInStatus: unknown(1), lineInOk(2), lineInFail(3), microphoneUnknown(4), microphoneConnected(5), microphoneDisconnected(6), microphoneShorted(7) || Once every 60 second || Panels || High || The Line In or Microphone status
 
|-
 
|-
| || notOperative(2) ||  ||  || |
+
| 1.3.6.1.4.1.26122.3.9 || '''controlInput''' ||  ||  || ||  
 
|-
 
|-
| || channelOk(3) || || || |
+
| 1.3.6.1.4.1.26122.3.9.1 || controlInputCount || During startup || ESC + ENA || || Number of Control Input entries in controlInputTable
 
|-
 
|-
| || channelFail(4) || || || |
+
| 1.3.6.1.4.1.26122.3.9.2.1.2 || controlInputString || During startup || ESC + ENA || || The name of the Control Input
 
|-
 
|-
| || channelShutdown(5) || || || |
+
| 1.3.6.1.4.1.26122.3.9.2.1.3 || controlInputStatus: unknown(1), open(2), closed(3), failShorted(4), failOpen(5) || Once every 60 second || ESC + ENA || High || The Control Input status
 
|-
 
|-
|  || channelGracefulDegradation(6) || || || |
+
| 1.3.6.1.4.1.26122.3.10 || '''controlOutput''' ||  ||  || ||
 +
|-
 +
| 1.3.6.1.4.1.26122.3.10.1 || controlOutputCount || During startup || ESC + ENA || || Number of Control Output entries in controlOutputTable
 +
|-
 +
| 1.3.6.1.4.1.26122.3.10.2.1.2 || controlOutputString || During startup || ESC + ENA || || The name of the Control Output
 +
|-
 +
| 1.3.6.1.4.1.26122.3.10.2.1.3 || controlOutputStatus: unknown(1), notActive(2), active(3), failNotActive(4), failActive(5) || Once every 60 second || ESC + ENA || || The Control Output status
 
|-
 
|-
 
|}
 
|}
  
 +
=Download=
 +
Download the MIB from the [[Downloads#SNMP_Device_MIB|download page]]
 +
 +
== Additional Documentation ==
 +
[https://wiki.zenitel.com/wiki/SNMP_in_IP_Stations SNMP in IP Stations] <br>
 +
[[SNMP_Device_MIB | SNMP Device MIB]]
  
 
[[Category:Integration]]
 
[[Category:Integration]]
 
[[Category:Exigo features]]
 
[[Category:Exigo features]]

Latest revision as of 09:31, 13 June 2019

This article describes the SNMP parameters that are recommended to monitor.


Exigo 1.2.3.13

Exigo 1.2.3.13 is using SNMPv1.

OID Logical name Frequency Unit Priority Description
1.3.6.1.4.1.26122.3.1.4 infoAmplifierType During startup All The device Amplifier Type
1.3.6.1.4.1.26122.3.1.1 infoPackageVersion During startup All The device Package Version
1.3.6.1.4.1.26122.3.2 temp
1.3.6.1.4.1.26122.3.2.1 tempTableCount Number of Temperature entries in tempTable
1.3.6.1.4.1.26122.3.2.2.1.2 tempSensorName During startup SSC + ENA The name of the temperature sensor we are reading
1.3.6.1.4.1.26122.3.2.2.1.7 tempAverageString During startup SSC + ENA The average temperature
1.3.6.1.4.1.26122.3.2.2.1.8 tempAverageValue Twice every 60 second SSC + ENA The average temperature of this sensor in the device
1.3.6.1.4.1.26122.3.3 fan
1.3.6.1.4.1.26122.3.3.1 fanTableCount During startup SSC + ENA Number of Fan entries in fanTable
1.3.6.1.4.1.26122.3.3.2.1.2 fanString During startup SSC + ENA The name of the fan sensor we are reading
1.3.6.1.4.1.26122.3.3.2.1.3 fanValue Once every 60 second SSC + ENA The rotation speed of the fan in RPM
1.3.6.1.4.1.26122.3.7 ampChannel
1.3.6.1.4.1.26122.3.7.1 ampChannelCount During startup ENA The total number of Amplifier channels
1.3.6.1.4.1.26122.3.7.3.1.2 ampChannelString During startup ENA The name of the Amplifier channel
1.3.6.1.4.1.26122.3.7.3.1.3 ampChannelStatus: unknown(1), notOperative(2), channelOk(3), channelFail(4), channelShutdown(5), channelGracefulDegradation(6) Once every 60 second ENA High The Amplifier Channel status
1.3.6.1.4.1.26122.3.6 lineIn Panels
1.3.6.1.4.1.26122.3.6.1.1.5 lineInStatus: unknown(1), lineInOk(2), lineInFail(3), microphoneUnknown(4), microphoneConnected(5), microphoneDisconnected(6), microphoneShorted(7) Once every 60 second Panels High The Line In or Microphone status
1.3.6.1.4.1.26122.3.9 controlInput
1.3.6.1.4.1.26122.3.9.1 controlInputCount During startup ESC + ENA Number of Control Input entries in controlInputTable
1.3.6.1.4.1.26122.3.9.2.1.2 controlInputString During startup ESC + ENA The name of the Control Input
1.3.6.1.4.1.26122.3.9.2.1.3 controlInputStatus: unknown(1), open(2), closed(3), failShorted(4), failOpen(5) Once every 60 second ESC + ENA High The Control Input status
1.3.6.1.4.1.26122.3.10 controlOutput
1.3.6.1.4.1.26122.3.10.1 controlOutputCount During startup ESC + ENA Number of Control Output entries in controlOutputTable
1.3.6.1.4.1.26122.3.10.2.1.2 controlOutputString During startup ESC + ENA The name of the Control Output
1.3.6.1.4.1.26122.3.10.2.1.3 controlOutputStatus: unknown(1), notActive(2), active(3), failNotActive(4), failActive(5) Once every 60 second ESC + ENA The Control Output status

Download

Download the MIB from the download page

Additional Documentation

SNMP in IP Stations
SNMP Device MIB