Difference between revisions of "Release Note Exigo 1.4"
(→Software included in EXIGO-1.4.3.8.zip) |
(→Exigo 1.4.3.8) |
||
Line 2: | Line 2: | ||
Release status: Official, available | Release status: Official, available | ||
− | Release date: 07. | + | Release date: 07.09.2020 |
Software collection file: EXIGO-1.4.3.8.zip | Software collection file: EXIGO-1.4.3.8.zip | ||
Line 40: | Line 40: | ||
==== New STICK (SIM) Card does not work for Exigo ==== | ==== New STICK (SIM) Card does not work for Exigo ==== | ||
The new STICK card requires an updated driver in order for the system to read it correctly. The driver is updated and will now work with the new STICK. | The new STICK card requires an updated driver in order for the system to read it correctly. The driver is updated and will now work with the new STICK. | ||
− | |||
− | |||
= Exigo 1.4.3.7 = | = Exigo 1.4.3.7 = |
Revision as of 10:38, 7 September 2020
Contents
- 1 Exigo 1.4.3.8
- 2 Exigo 1.4.3.7
- 3 Exigo 1.4.3.6
- 4 Exigo 1.4.3.5
- 4.1 Software included in EXIGO-1.4.3.5.zip
- 4.2 New Features
- 4.3 Bugfixes and improvements
- 4.3.1 Pilot tone turned off during suspend monitoring
- 4.3.2 Amplifier Class D chip may crash when analog bypass is used
- 4.3.3 Improved System Controller performance
- 4.3.4 "Disable AVC" input-action creates toggle-action on key press_action event
- 4.3.5 EMT: "Recall, Record" input action did not display "Wait for PTT flag"
- 4.3.6 Program name change was not updated in configuration tree
- 4.4 Known issues
- 4.4.1 EAPIR-8 The Microphone input is not working
- 4.4.2 Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
- 4.4.3 Tick tone will not be played out on access panels which is part of a zone
- 4.4.4 SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
- 4.4.5 The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
- 4.4.6 Flowire - For turning of monitoring of Flowire devices completely a full chilly restart must be done
- 4.4.7 EMT - Only one dialog box can be open if more than one EMT version is open
- 5 Exigo 1.4.3.4
- 5.1 Software included in EXIGO-1.4.3.4.zip
- 5.2 Bugfixes and improvements
- 5.3 Known issues
- 5.3.1 EAPIR-8 The Microphone input is not working
- 5.3.2 Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
- 5.3.3 Tick tone will not be played out on access panels which is part of a zone
- 5.3.4 SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
- 5.3.5 The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
- 5.3.6 Flowire - For turning of monitoring of Flowire devices completely a full chilly restart must be done
- 5.3.7 EMT - Only one dialog box can be open if more than one EMT version is open
- 6 Exigo 1.4.3.3
- 6.1 Software included in EXIGO-1.4.3.3.zip
- 6.2 Bugfixes and improvements
- 6.3 Known issues
- 6.3.1 Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
- 6.3.2 Tick tone will not be played out on access panels which is part of a zone
- 6.3.3 SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
- 6.3.4 The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
- 6.3.5 Flowire - For turning of monitoring of Flowire devices completely a full chilly restart must be done
- 6.3.6 EMT - Only one dialog box can be open if more than one EMT version is open
- 7 Exigo 1.4.3.2
- 7.1 Software included in EXIGO-1.4.3.2.zip
- 7.2 Bugfixes and improvements
- 7.3 Known issues
- 7.3.1 Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
- 7.3.2 Tick tone will not be played out on access panels which is part of a zone
- 7.3.3 SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
- 7.3.4 The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
- 7.3.5 Flowire - For turning of monitoring of Flowire devices completely a full chilly restart must be done
- 7.3.6 EMT - Only one dialog box can be open if more than one EMT version is open
- 8 Exigo 1.4.3.1
- 8.1 Software included in EXIGO-1.4.3.1.zip
- 8.2 Bugfixes and improvements
- 8.2.1 SIP Trunk Stations Should Only Use Trunk License
- 8.2.2 Lamp test would adversly affect time-limited blinking leds
- 8.2.3 Unicast was missing call information related to volume settings
- 8.2.4 SNMPv2c getBulkrequest issues fixed
- 8.2.5 Issue related to multiple call escalations
- 8.2.6 Fixed issue with HD-Mode where audio would leak between two channels on one amplifier
- 8.2.7 VAD configured on a line input will no longer trigger "read ip adress" if a control input is shorted
- 8.2.8 VAD will now continue to work after a reboot
- 8.2.9 ReCall from SIP trunk
- 8.2.10 ZAP can now be used to set volume levels on all amplifiers and kits
- 8.2.11 Volume override can now be used correctly with advanced volume control
- 8.2.12 Fixed memory leak on control inputs with external fault
- 8.2.13 Option "Replace" on call type Live Speech
- 8.3 Known issues
- 8.3.1 Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
- 8.3.2 Tick tone will not be played out on access panels which is part of a zone
- 8.3.3 SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
- 8.3.4 The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
- 8.3.5 Flowire - For turning of monitoring of flowire devices completly a full chilly restart must be done
- 8.3.6 EMT - Only one dialog box can be open if more than one EMT version is open
- 9 Exigo 1.4.3.0
- 9.1 Software included in EXIGO-1.4.3.0.zip
- 9.2 New Features
- 9.2.1 IP-LCM support in Alphacom / Pulse / SIP
- 9.2.2 Exigo systems can now be integrated with Pulse systems
- 9.2.3 EMT - Scan IP range for devices now available
- 9.2.4 SNMP traps are now supported by all Exigo devices
- 9.2.5 Exigo now supports distributed automatic volume controllers
- 9.2.6 ENA2100-AC is now supported in Exigo systems
- 9.2.7 New ZAP rpcs available for remote integration
- 9.2.8 Audio bypass is now supported on all Exigo devices
- 9.2.9 Zone select can now deselect when activities are started or stopped
- 9.2.10 Adjustable delay of missing devices
- 9.3 Bugfixes and improvements
- 9.3.1 Detailed channel state in SNMP MIB
- 9.3.2 Access panels part of zones can now correctly receive messages, alarms and live speech
- 9.3.3 EMT - Database will handle Exigo Net system ID settings better
- 9.3.4 EMT - An error window without effect would sometimes appear when changing the name of a zone
- 9.3.5 EMT - Actions can now be copied to paired devices successfully
- 9.3.6 Headphone output on ENA2200 and ENA2400 will now not be active unless activated from the GUI
- 9.3.7 Improved handling of audio streams on amplifiers
- 9.3.8 EMT - "Always include" field removed from local mute action
- 9.3.9 AMC-IP will now correctly remove Exigo settings immediatly after a factory default
- 9.3.10 EMT - Password for PSC can now be changed
- 9.3.11 EMT - Advanced program control sequence can now be correctly copy/pasted
- 9.3.12 TKIE-2 relay 2 can now be configured correctly without rebooting the device
- 9.3.13 Program volume control function can now use dynamically selected zones
- 9.3.14 EMT - PSC will now reboot correctly if changes to the SIP interface is done
- 9.3.15 EMT - Tooltip for zone selection is now correct
- 9.3.16 EMT - EMT can now correclty generate a database directly from a GET when controller B is missing
- 9.3.17 EMT - Zone names with illegal characters will now not be allowed
- 9.3.18 Incoming SIP Calls will now be correctly parsed
- 9.3.19 EMT - Name of zone will now always save when the done button is pressed
- 9.3.20 EMT - Improvements to zone handling when an access panel is added to the zone
- 9.3.21 Voice activity detection can now be used on EX panels to automatically trigger actions
- 9.3.22 EMT - Getting a database from a running system will now correctly get any volume adjustments done to the Exigo amplifiers
- 9.3.23 EMT - Databases made with EMT 1.4 will now correctly set "use global settings" for SNMP on all devices
- 9.3.24 Control outputs can now be correctly reconfigured from fault indication to audio activity without rebooting the device
- 9.3.25 Volume control normalized for IP speakers and Exigo amplifiers
- 9.3.26 Various typos fixed in fault message for ESC1 GUI
- 9.3.27 EMT - Volume settings are now availabile on all devices
- 9.3.28 EMT - Exigo 1.2 Databases can now be opened in EMT 1.4 and newer
- 9.3.29 EMT - Parallel wired devices will now be correctly configured
- 9.3.30 ESC1 - All latin letters including æøå supported in GUI
- 9.3.31 Exigo database is now completely deleted from AMC-IP board during a factory default
- 9.3.32 ESC1 - Internal network recovery mechanisms added
- 9.3.33 EMT - Volume Override Priority was not corectly fetched from the PSC with a GET operation
- 9.3.34 Programs will now merge correctly regardless of how Zone Selection is set up
- 9.3.35 Live speech will now always start correctly after a "rejected" call
- 9.3.36 Recall is now correctly timing out if timeout is used
- 9.3.37 EMT - Clear all activity will now not have destination field if "all" is selected
- 9.3.38 EMT - Adding an amplifier to more than one zone will now always generate a "multiple zones" warning
- 9.3.39 Live speech with "wait for PTT" and no dynamic zones selected will now not light the green led
- 9.3.40 Non-existing power sources reported as faulty
- 9.3.41 ECPIR volume settings can now be adjusted even if the access panel is not connected to a server
- 9.3.42 Call escalation with no zones selected will now correctly be ignored instead of crashing the access panel
- 9.3.43 Exigo devices will now listen to the same NTP server if more than one is configured
- 9.3.44 (Bug 1.3.3.1) Dummy zones which does not contain devices can now be correctly called again
- 9.3.45 EMT - Keys on main panel will sort first for devices which use EMBDR-8
- 9.3.46 EMT - Zones could loose name if "done" was not pressed
- 9.3.47 The list of possible faults on the Exigo wiki is now updated
- 9.3.48 EMT - Volume settings for access panels available
- 9.3.49 EMT will automatically reset AMC-IP when new SIP devices have been added
- 9.3.50 Exigo Amplifier web pages and SNMP text normalized
- 9.3.51 It is now possible to configure which call states that follow alarm should operate in
- 9.3.52 Volume adjustment function now blink green one time to indicate a change and red if limit is met
- 9.3.53 EMT now shows version in window name
- 9.3.54 Increased system capacity
- 9.3.55 SIP advance integration: Call id
- 9.3.56 The Configure Stations menu on the AMC-IP web is now disabled in Exigo Mode
- 9.4 Known issues
- 9.4.1 Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
- 9.4.2 Tick tone will not be played out on access panels which is part of a zone
- 9.4.3 SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
- 9.4.4 The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
- 9.4.5 Flowire - For turning of monitoring of Flowire devices completely a full chilly restart must be done
- 9.4.6 EMT - Only one dialog box can be open if more than one EMT version is open
- 9.4.7 Access panel set in HD-mode with MB30G will not work correctly and audio might be corrupted
Exigo 1.4.3.8
Release status: Official, available Release date: 07.09.2020 Software collection file: EXIGO-1.4.3.8.zip
Software included in EXIGO-1.4.3.8.zip
Product | Version | Product description |
VSF-Turbine | VSFT-4.10.3.6 | Firmware for the following devices: ESC1(Secondary System Controller), ENA2100, ENA2200, ENA2400, ECPIR-3P, ECPIR-P, EAPIR-8, EAPFX-1, EAPFX-6, EAPII-1, EAPII-6, TKIS-2, TKIE-2, IP-LCM. |
AlphaSys Firmware | 13.0.3.11 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) alpha-sys_13.0.3.11.apkg, bsp_32.2.3.5.apkg |
VS-EMT Exigo Management Tools | EMT-1.4.3.8 | Configuration tool, installed on a Windows PC |
VSF-Inca | 02.20.3.12 | Special Exigo software for the CRM-V based panel |
VS-DEVICE-MIB | 201806190000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
Bugfixes and improvements
New STICK (SIM) Card does not work for Exigo
The new STICK card requires an updated driver in order for the system to read it correctly. The driver is updated and will now work with the new STICK.
Exigo 1.4.3.7
Release status: LA Release date: 28.08.2020 Software collection file: EXIGO-1.4.3.7.zip
Software included in EXIGO-1.4.3.7.zip
Product | Version | Product description |
VSF-Turbine | VSFT-4.10.3.6 | Firmware for the following devices: ESC1(Secondary System Controller), ENA2100, ENA2200, ENA2400, ECPIR-3P, ECPIR-P, EAPIR-8, EAPFX-1, EAPFX-6, EAPII-1, EAPII-6, TKIS-2, TKIE-2, IP-LCM. |
AlphaSys Firmware | 13.0.3.10 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) |
VS-EMT Exigo Management Tools | EMT-1.4.3.8 | Configuration tool, installed on a Windows PC |
VSF-Inca | 02.20.3.12 | Special Exigo software for the CRM-V based panel |
VS-DEVICE-MIB | 201806190000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
Bugfixes and improvements
ENA2xxx Channel 2 failed to report Line Status as Warning
Regression where channel 2 reported line status as fault, even though configured to report it as warning, is corrected.
Exigo 1.4.3.6
Release status: LA Release date: 01.07.2020 Software collection file: EXIGO-1.4.3.6.zip
Software included in EXIGO-1.4.3.6.zip
Product | Version | Product description |
VSF-Turbine | VSFT-4.10.3.5 | Firmware for the following devices: ESC1(Secondary System Controller), ENA2100, ENA2200, ENA2400, ECPIR-3P, ECPIR-P, EAPIR-8, EAPFX-1, EAPFX-6, EAPII-1, EAPII-6, TKIS-2, TKIE-2, IP-LCM. |
AlphaSys Firmware | 13.0.3.10 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) |
VS-EMT Exigo Management Tools | EMT-1.4.3.8 | Configuration tool, installed on a Windows PC |
VSF-Inca | 02.20.3.12 | Special Exigo software for the CRM-V based panel |
VS-DEVICE-MIB | 201806190000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
Bugfixes and improvements
Duplicate Device function
The Duplicate Device function in EMT would not generate new StId's for the new device, so that multiple devices would have the same StId
Not possible to configure Backup Amplifier
Adding a Backup Amplifier to the configuration in EMT would fail with an error message.
Live Speech Input Action on CIO fails
It was not possible to configure Live Speech Input Action on Panel and Kit CIO's
Copy/Paste Output Action with custom description
If CO with custom description is copy/pasted, it would result in some missing configuration.
Optimized call setup-time
System controller software has been updated and optimized in order to keep the call set-up time low, even if a large number of BGM feeds are active.
Exigo 1.4.3.5
Release status: Official, available Release date: 13.03.2020 Software collection file: EXIGO-1.4.3.5.zip
Software included in EXIGO-1.4.3.5.zip
Product | Version | Product description |
VSF-Turbine | VSFT-4.10.3.5 | Firmware for the following devices: ESC1(Secondary System Controller), ENA2100, ENA2200, ENA2400, ECPIR-3P, ECPIR-P, EAPIR-8, EAPFX-1, EAPFX-6, EAPII-1, EAPII-6, TKIS-2, TKIE-2, IP-LCM. |
AlphaSys Firmware | 13.0.3.9 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) |
VS-EMT Exigo Management Tools | EMT-1.4.3.7 | Configuration tool, installed on a Windows PC |
VSF-Inca | 02.20.3.12 | Special Exigo software for the CRM-V based panel |
VS-DEVICE-MIB | 201806190000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
New Features
Modbus interface
The Exigo Controller implements a Modbus TCP slave (server) interface on the standard Modbus port, TCP port 502. The Modbus interface in Exigo has two main features:
- Status about amplifiers and panels connected to the Controller can be read from a 16 bit Modbus Input Register.
- PA calls and announcements can be triggered by writing to a Modbus Coil Register.
Configuration of PA Calls and announcements is done through EMT.
Option to configure delay for Exigo Network Amplifiers
It is now possible to add delay per channel per Exigo Network Amplifier.
Bugfixes and improvements
Pilot tone turned off during suspend monitoring
The pilot tone is turned off during suspend monitoring if no LETs in the system.
Amplifier Class D chip may crash when analog bypass is used
When analog bypass is used on ENA2200/ENA2400, audio filters were not active which could cause Class D chip to crash. Analog bypass is now changed to Digital (SW) bypass that applies audio filters.
In Exigo Management Tool, the Amplifier output channel setting "HW Bypass Mode" on all ENA amplifier types is renamed to "Bypass Mode".
Also, the Bypass Mode can now be set individually for each Amplifier output channel on all ENA device types.
Improved System Controller performance
Improved startup procedure in Exigo System Controller to allow loading of large configuration databases.
"Disable AVC" input-action creates toggle-action on key press_action event
When adding the "Disable AVC" input-action to a key node, EMT previously created a start-action on the press_action event and stop-action on the release_action event. The behavior is changed so that a single toggle-action is created on the press_action event; nothing is triggered by the release_action event. In effect, this changes the AVC function to be disabled with one press on the configured key, and re-enabled with a consecutive press.
EMT: "Recall, Record" input action did not display "Wait for PTT flag"
In EMT, when dropping a "Recall, Record" input action onto a Control Input, the "Wait for PTT" flag was not displayed. It was correctly displayed when dropped onto a CI on_action or off_action.
Program name change was not updated in configuration tree
EMT needed to restart/reload database for an updated program name to be displayed correctly in the configuration tree.
Known issues
EAPIR-8 The Microphone input is not working
Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
Tick tone will not be played out on access panels which is part of a zone
SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
Flowire - For turning of monitoring of Flowire devices completely a full chilly restart must be done
EMT - Only one dialog box can be open if more than one EMT version is open
Exigo 1.4.3.4
Release status: Official, available Release date: 04.11.2019 Software collection file: EXIGO-1.4.3.4.zip
Software included in EXIGO-1.4.3.4.zip
Product | Version | Product description |
VSF-Turbine | VSFT-4.10.3.4 | Firmware for the following devices: ESC1(Secondary System Controller), ENA2100, ENA2200, ENA2400, ECPIR-3P, ECPIR-P, EAPIR-8, EAPFX-1, EAPFX-6, EAPII-1, EAPII-6, TKIS-2, TKIE-2, IP-LCM. |
AlphaSys Firmware | 13.0.3.7 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) |
VS-EMT Exigo Management Tools | EMT-1.4.3.4 | Configuration tool, installed on a Windows PC |
VSF-Inca | 02.20.3.12 | Special Exigo software for the CRM-V based panel |
VS-DEVICE-MIB | 201806190000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
Bugfixes and improvements
Backup Amplifier Remote Control
There is a new function to control Take Over and Release functions of Backup Amplifiers. The function is available in EMT Operation Pane.
Option to pulse the SSC fault relay on new faults
Added an option for the SSC fault relay to pulse (turn off and on again) on new faults, or when faults reappear.
External relay for industrial stations not working
This is now corrected and the correct gpio is now used for external relays
Known issues
EAPIR-8 The Microphone input is not working
Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
Tick tone will not be played out on access panels which is part of a zone
SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
Flowire - For turning of monitoring of Flowire devices completely a full chilly restart must be done
EMT - Only one dialog box can be open if more than one EMT version is open
Exigo 1.4.3.3
Release status: Official, available Release date: 03.09.2019 Software collection file: EXIGO-1.4.3.3.zip
Software included in EXIGO-1.4.3.3.zip
Product | Version | Product description |
VSF-Turbine | VSFT-4.10.3.2 | Firmware for the following devices: ESC1(Secondary System Controller), ENA2100, ENA2200, ENA2400, ECPIR-3P, ECPIR-P, EAPIR-8, EAPFX-1, EAPFX-6, EAPII-1, EAPII-6, TKIS-2, TKIE-2, IP-LCM. |
AlphaSys Firmware | 13.0.3.6 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) |
VS-EMT Exigo Management Tools | EMT-1.4.3.2 | Configuration tool, installed on a Windows PC |
VSF-Inca | 02.20.3.12 | Special Exigo software for the CRM-V based panel |
VS-DEVICE-MIB | 201806190000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
Bugfixes and improvements
Exigo Controller DSP Fault Result in Missing Audio
In the unlikely situation of the A-Controller DSP processor stops working, audio from messages and alarm generator will be missing.
This situation is now avoided by lowering priority of the A-controller when DSP fault detected. This will assure usage of B-controller audio in the system.
Known issues
Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
Tick tone will not be played out on access panels which is part of a zone
SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
Flowire - For turning of monitoring of Flowire devices completely a full chilly restart must be done
EMT - Only one dialog box can be open if more than one EMT version is open
Exigo 1.4.3.2
Release status: LA Release date: 27.06.2019 Software collection file: EXIGO-1.4.3.2.zip
Software included in EXIGO-1.4.3.2.zip
Product | Version | Product description |
VSF-Turbine | VSFT-4.10.3.2 | Firmware for the following devices: ESC1(Secondary System Controller), ENA2100, ENA2200, ENA2400, ECPIR-3P, ECPIR-P, EAPIR-8, EAPFX-1, EAPFX-6, EAPII-1, EAPII-6, TKIS-2, TKIE-2, IP-LCM. |
AlphaSys Firmware | 13.0.3.4 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) |
VS-EMT Exigo Management Tools | EMT-1.4.3.2 | Configuration tool, installed on a Windows PC |
VSF-Inca | 02.20.3.12 | Special Exigo software for the CRM-V based panel |
VS-DEVICE-MIB | 201806190000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
Bugfixes and improvements
Configurable Cancel Tone on Live Speech
- New EMT system setting for turning off the audible cancel tone played out in the Panel after live speech. Default setting is ON.
Use IP Speaker as AVC Source
- It is now possible to use AVC Source Device as AVC Receiver. This makes it possible to connect a microphone to an IP Speaker and use this as AVC Source Device.
ENA2100-AC was missing a critical high pass filter
- This could lead to destroying the class-d modules with audio in low frequencies
Known issues
Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
Tick tone will not be played out on access panels which is part of a zone
SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
Flowire - For turning of monitoring of Flowire devices completely a full chilly restart must be done
EMT - Only one dialog box can be open if more than one EMT version is open
Exigo 1.4.3.1
Release status: LA Release date: 27.05.2019 Software collection file: EXIGO-1.4.3.1.zip
Software included in EXIGO-1.4.3.1.zip
Product | Version | Product description |
VSF-Turbine | VSFT-4.10.3.1 | Firmware for the following devices: ESC1(Secondary System Controller), ENA2100, ENA2200, ENA2400, ECPIR-3P, ECPIR-P, EAPIR-8, EAPFX-1, EAPFX-6, EAPII-1, EAPII-6, TKIS-2, TKIE-2, IP-LCM. |
AlphaSys Firmware | 13.0.3.3 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) |
VS-EMT Exigo Management Tools | EMT-1.4.3.0 | Configuration tool, installed on a Windows PC |
VSF-Inca | 02.20.3.12 | Special Exigo software for the CRM-V based panel |
VS-DEVICE-MIB | 201806190000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
Bugfixes and improvements
SIP Trunk Stations Should Only Use Trunk License
- SIP trunk stations now allocate SIP trunk license when in call. Previously each configured SIP trunk station required a SIP station license.
- For customers using SIP trunk stations, previously used SIP station licenses will not be used after upgrade.
- The maximum number of simultaneous SIP trunk stations in call, will relate to the number of SIP trunk licenses in the system.
- Please consult Customer Service if SIP station licenses needed to be converted to SIP trunk licenses.
Lamp test would adversly affect time-limited blinking leds
- LED's which were blinking (example due to a live speech timeout) would lock and continue to blink after the lamp test was finished.
- Volume settings would not work on Exigo amplifiers set to receive unicast from PSC
SNMPv2c getBulkrequest issues fixed
- SNMP now correctly handles bulk requests with multiple OID which goes beyond one OID. This would previously crash the SNMP process and restart the device.
- Fixed an issue where multiple call escalation IDs on a call with always include zones and clear call escalation on first activity would not work correctly in combination.
Fixed issue with HD-Mode where audio would leak between two channels on one amplifier
- Exigo systems under high load could in some cases send PA messages in some additional zones for a few seconds.
VAD configured on a line input will no longer trigger "read ip adress" if a control input is shorted
- Fixed an issue where configured VAD would cause the amplifier to read its IP-address if the amplifier was started before the PSC was ready.
VAD will now continue to work after a reboot
- VAD stopped working after a reboot due to a mismatch in configuration
ReCall from SIP trunk
- Activating the ReCall function from a SIP trunk using codec G711, did not play out the recorded message. Fixed.
ZAP can now be used to set volume levels on all amplifiers and kits
Volume override can now be used correctly with advanced volume control
- Volume override can now be used both on channels and zones to force max volume if an activity has a priority above a configured level
Fixed memory leak on control inputs with external fault
- Device with a external fault on a control input would reboot after around 9000 activations due to a memory leak in libstpanels json handling.
Option "Replace" on call type Live Speech
It is now possible to use the option Replace on call type Live Speech.
Known issues
Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
Tick tone will not be played out on access panels which is part of a zone
SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
Flowire - For turning of monitoring of flowire devices completly a full chilly restart must be done
EMT - Only one dialog box can be open if more than one EMT version is open
Exigo 1.4.3.0
Release status: Official, available Release date: 10.12.2018 Software collection file: EXIGO-1.4.3.0.zip
Software included in EXIGO-1.4.3.0.zip
Product | Version | Product description |
VSF-Turbine | VSFT-4.10.3.0 | Firmware for the following devices: ESC1(Secondary System Controller), ENA2100, ENA2200, ENA2400, ECPIR-3P, ECPIR-P, EAPIR-8, EAPFX-1, EAPFX-6, EAPII-1, EAPII-6, TKIS-2, TKIE-2, IP-LCM. |
AlphaSys Firmware | 13.0.3.0 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) |
VS-EMT Exigo Management Tools | EMT-1.4.3.0 | Configuration tool, installed on a Windows PC |
VSF-Inca | 02.20.3.12 | Special Exigo software for the CRM-V based panel |
VS-DEVICE-MIB | 201806190000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
New Features
IP-LCM support in Alphacom / Pulse / SIP
- IP-LCM is now supported in Exigo systems. This device have:
- 8 robust high power relays
- 8 robust inputs
- Powered via the TKIS-2 kit with PoE, PoE inject or external power supply
- All connections and features from the TKIS-2 kit available
Exigo systems can now be integrated with Pulse systems
- Using the SIP interface on Exigo systems allows for integration both ways to pulse systems
EMT - Scan IP range for devices now available
- New tool in Operation view to scan an IP range for Exigo devices. From the list of discovered devices it is possible to send a command to the device to make the fault led blink (works for ENA, Access Panel and SSC devices).
- By default, the fault led will blink 4 times, 2 blinks pr second. The number of blinks and blink rate can be changed in Options -> Configuration Options.
- From the list of discovered devices it is also possible to open the device's Web Configuration page in the default browser.
SNMP traps are now supported by all Exigo devices
- SNMP traps for faults are now supported by all Exigo devices. Configuration is done via EMT.
Exigo now supports distributed automatic volume controllers
- Distributed Automatic Volume Controllers (dAVC) is TKIS-2 kits which measures background noise in an area and can adjust the volume settings for an amplifier or IP speaker so that the audio is audible above the noise.
- DAVC devices is monitored as other devices in the Exigo system.
- Zones with dAVC devices can have "volume override" functionality. Activities with priorities above this threshold will use full volume efficiently ignore background noise adjustments.
- DAVC Control of zone can be based on: highest, average or average mid. Both average require at least four dAVC devices.
- Disable AVC function can be used to selectively disable dAVC functionality per zone.
- Adjustment mode can be positive or negative between two thresholds.
- Advanced options where attack rate, decay rate, hysteresis and lock out time are available
ENA2100-AC is now supported in Exigo systems
- Advanced line monitoring and Lets supported
- Hardware audio bypass supported
- 2 control outputs with 200mA@24Vdc each
- 2 control inputs
- Supported in Exigo mode and Alphacom systems
New ZAP rpcs available for remote integration
- Restart of Class-D module
- Identification of devices by toggling fault led
- Remote toggling of control outputs
Audio bypass is now supported on all Exigo devices
- Bypass will route audio directly from the line input to both audio output channels based on the following configuration choices:
- Always on: This allows the amplifier to operate standalone mode without ESC1 or Alphacom
- Idle: This allows the amplifier to have bypass activated when no digital audio is present.
- No connection: This allows the amplifier to activate bypass if it loose connection to ESC1 or Alphacom
- Always off: This is default for Exigo amplifiers and audio bypass will never be activated
- ENA2100-AC: Hardware bypass available for instant forwarding
- ENA2200, ENA2400-DC, ENA2400-AC: Audio bypass available after software is up
Zone select can now deselect when activities are started or stopped
- This gives more options to how zone select should behave in relation to activities started from the access panels
Adjustable delay of missing devices
- It is now possible on a per device level to adjust a delay before the device is reported missing. Default is 0 seconds of delay before the device is reported missing.
Bugfixes and improvements
Detailed channel state in SNMP MIB
- Detailed information about the actual state of the audio channel is now included in the SNMP MIB.
Access panels part of zones can now correctly receive messages, alarms and live speech
EMT - Database will handle Exigo Net system ID settings better
EMT - An error window without effect would sometimes appear when changing the name of a zone
EMT - Actions can now be copied to paired devices successfully
Headphone output on ENA2200 and ENA2400 will now not be active unless activated from the GUI
Improved handling of audio streams on amplifiers
EMT - "Always include" field removed from local mute action
AMC-IP will now correctly remove Exigo settings immediatly after a factory default
EMT - Password for PSC can now be changed
EMT - Advanced program control sequence can now be correctly copy/pasted
TKIE-2 relay 2 can now be configured correctly without rebooting the device
Program volume control function can now use dynamically selected zones
EMT - PSC will now reboot correctly if changes to the SIP interface is done
- A manual reboot was necessary for any changes to be enabled and this will happen automatically now.
EMT - Tooltip for zone selection is now correct
EMT - EMT can now correclty generate a database directly from a GET when controller B is missing
EMT - Zone names with illegal characters will now not be allowed
Incoming SIP Calls will now be correctly parsed
- Sometimes the source nummer of an incoming SIP call would add a digit
EMT - Name of zone will now always save when the done button is pressed
EMT - Improvements to zone handling when an access panel is added to the zone
Voice activity detection can now be used on EX panels to automatically trigger actions
EMT - Getting a database from a running system will now correctly get any volume adjustments done to the Exigo amplifiers
EMT - Databases made with EMT 1.4 will now correctly set "use global settings" for SNMP on all devices
Control outputs can now be correctly reconfigured from fault indication to audio activity without rebooting the device
Volume control normalized for IP speakers and Exigo amplifiers
- Adjusting volume in zones with volume controls will now result in the same volume reduction for both IP speakers and Exigo amplifiers
Various typos fixed in fault message for ESC1 GUI
EMT - Volume settings are now availabile on all devices
EMT - Exigo 1.2 Databases can now be opened in EMT 1.4 and newer
EMT - Parallel wired devices will now be correctly configured
ESC1 - All latin letters including æøå supported in GUI
Exigo database is now completely deleted from AMC-IP board during a factory default
ESC1 - Internal network recovery mechanisms added
- In some installations glitches could occur which would disable the network interface until a reboot. Recovery mechanisms have been added to ensure the continuing operation of the network interface in such cases.
EMT - Volume Override Priority was not corectly fetched from the PSC with a GET operation
Programs will now merge correctly regardless of how Zone Selection is set up
Live speech will now always start correctly after a "rejected" call
- (1.3.3.1) If a call was rejected the operator would have to press twice on the live speech button to set up a new call. This is now fixed.
Recall is now correctly timing out if timeout is used
EMT - Clear all activity will now not have destination field if "all" is selected
EMT - Adding an amplifier to more than one zone will now always generate a "multiple zones" warning
Live speech with "wait for PTT" and no dynamic zones selected will now not light the green led
Non-existing power sources reported as faulty
ECPIR volume settings can now be adjusted even if the access panel is not connected to a server
Call escalation with no zones selected will now correctly be ignored instead of crashing the access panel
Exigo devices will now listen to the same NTP server if more than one is configured
(Bug 1.3.3.1) Dummy zones which does not contain devices can now be correctly called again
EMT - Keys on main panel will sort first for devices which use EMBDR-8
EMT - Zones could loose name if "done" was not pressed
The list of possible faults on the Exigo wiki is now updated
EMT - Volume settings for access panels available
EMT will automatically reset AMC-IP when new SIP devices have been added
Exigo Amplifier web pages and SNMP text normalized
It is now possible to configure which call states that follow alarm should operate in
Volume adjustment function now blink green one time to indicate a change and red if limit is met
EMT now shows version in window name
Increased system capacity
- Exigo now supports up to 16 simultanious audio activities.
SIP advance integration: Call id
- Exigo will now strip all non-numeric characters from SIP calls
Known issues
Fault indication - It is possible to change from "or" to "and" between fields, but not inside one field
Tick tone will not be played out on access panels which is part of a zone
SIP devices for integration can only have directory numbers with numbers. Alphanumeric numbers are not supported
The same fault ID can not be used on different buttons on an access panel - This will result in wrong LED behavior
Flowire - For turning of monitoring of Flowire devices completely a full chilly restart must be done
EMT - Only one dialog box can be open if more than one EMT version is open
Access panel set in HD-mode with MB30G will not work correctly and audio might be corrupted
- All access panels are now default set to Voice mode to prevent errors.