Follow Any Alarm Tone

From exigoWiki
Jump to navigation Jump to search
The control output follows the alarm tone in Zone 1

The Follow Any Alarm Tone function is used to trigger the control output to follow one, many or any Alarm Tone in one specific zone.
It differs from Output Action Follow One Alarm Tone in that it can only follow alarms in one zone.

Make sure that alarm following will only work for alarms that originate from the digital alarm generator.

This function can be useful in providing visual indications in noisy areas.


Assigning Follow Any Alarm Tone to a Control Output

To assign the function Follow Any Alarm Tone to a Control Output:

  1. In Components view, open Output Actions
  2. In System, identify the Controller, the Amplifier or the Access Panel to be used, and expand to Device > Control Outputs
  3. Drag Follow Any Alarm Tone to the Control Output you want to use.
Assigning Follow Any Alarm Tone function to a Control Output


Configuration

Follow Alarm Tone in Zone 1

  1. Drag Follow Any Alarm Tone to the desired Control Output
  2. Select the desired Alarm (or Any) in Source
  3. Select Zone 1 in Zone
The specified alarm tone in Zone 1 will trigger Control Output 1


In this example General Alarm, Ship in Zone 1 will trigger Control Output 1.

Parameter Details

Idle State
Sets the idle state for the output. The options are Normally Open or Normally Closed

Source
The source that will trigger the alarm output. If Source is not specified, it will be ignored when checking whether the conditions for the audio activity triggering are present or not.

Zone
The zones in which the output on an activity is triggered. If Zone is not specified, it will be ignored when checking whether the conditions for the audio activity triggering are present or not. Note that only one zone can be specified.

Priority Range
The priority range within which the activity is triggered.

Follow Alarm Tone
If this is enabled the control output will toggle in tune with the alarm generator. If it is NOT enabled it will toggle on when the alarm is started and stay on until it ends.

Advanced Options:

Limit High Not OK: When the Control Output is cleared, and feedback voltage is at or above this value, the output is considered fed with alien voltage.
Limit Low OK: When the Control Output is set, and feedback voltage is above this value, the output is considered active OK.
On Lost Connection: Fall back to this state on lost connection with ESC. Available Settings: Idle State, No Change, Open, Closed.

Example of Use:

Case 1: Any Alarm in One Zone

It is common in noisy areas to add flashing lights or beacons which will indicate when there is activity on the PA.
The "follow any alarm" function can in this case be used to pulse the flashing light in the same pattern as a any alarm sent to the zone.
The configuration will then have:

  • Source:
  • Zone: "Noisy zone 1"
  • Priority Range: 1-40
  • Follow Alarm Tone: checked

Leaving Source empty will indicate that any alarm shall toggle this. With this setup the control output will trigger in the same pattern as any alarm tone sent to the zone.
For a general alarm (7 short burst, one long burst) the people in the area will then see the type of alarm which is active.

Case 2: Two Alarms in One Zone

It is common in noisy areas to add flashing lights or beacons which will indicate when there is activity on the PA.
The "follow any alarm" function can in this case be used to pulse the flashing light in the same pattern as a any alarm sent to the zone.
The configuration will then have:

  • Source: General Alarm, MOB alarm
  • Zone: "Noisy zone 1"
  • Priority Range: 1-40
  • Follow Alarm Tone: checked

With this setup the control output will trigger in the same pattern as either the General Alarm or the MOB alarm sent to the "Noisy zone 1" zone. The people in the area will then see the type of alarm that is active.