Release Notes Exigo 1.7

From exigoWiki
Revision as of 10:04, 27 April 2023 by Rlorentzen (talk | contribs) (Exigo 1.7.3.0)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search

Exigo 1.7.3.2

Release status: Official, available
Release date: 26.04.2023
Software collection file: EXIGO-1.7.3.2.zip

Software included in EXIGO-1.7.3.2.zip

Product Version Product description
VSF-Turbine VSFT-PA.6.5.3.6 Firmware for the following devices:
ESC1 (Secondary System Controller), ENA2100-AC, ENA2200, ENA2200-AC2, ENA2400-AC, ENA2400-AC2, ENA2400-DC, 1670,
EAPIR-8, ECPIR-P, ECPIR-3P, EBMDR-8, EAPFX-1, EAPFX-1-V2, EAPFX-6, EAPFX-6-V2, EAPII-1, EAPII-6,
AVC Source Device, IP Speaker, TKIS-2, TKIE-2, IP-LCM, TA-10.
VSFX 1.2.3.7 Firmware for ICX-500 PSC
AlphaSys Firmware 13.0.3.16 Firmware for the ESC1 (Primary System Controller/AMC-IP board) alpha-sys_13.0.3.16.apkg, bsp_32.2.3.6.apkg
VS-EMT Exigo Management Tools EMT-1.7.3.2 Configuration tool, installed on a Windows PC
VS-DEVICE-MIB 202203070000Z SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools


New Feature

None

Enhancements and Fixed Issues

MTN-4066 ENA2x00-AC2: Improved speaker line monitoring (SLM) on long speaker lines

The speaker line monitoring (SLM) measurements on long speaker lines (technical perspective up to 800nF) have been improved.

MTN-3987 ENA2x00-AC2: Adjustable ground fault limit

Detection limit can be set from terminal. Default is 100kohm.

MTN-3982 ENA2x00-AC2: Removed occurrence of false ground fault detection

During calibration of systems with long speaker lines, detection of false ground fault could occur. This would again prevent the calibration of the speaker lines. The occurrence of false ground faults is no longer present.

Known Issues

None


Exigo 1.7.3.0

Release status: Official, available
Release date: 13.12.2022
Software collection file: EXIGO-1.7.3.0.zip

Software included in EXIGO-1.7.3.0.zip

Product Version Product description
VSF-Turbine VSFT-PA.6.5.3.5 Firmware for the following devices:
ESC1 (Secondary System Controller), ENA2100-AC, ENA2200, ENA2200-AC2, ENA2400-AC, ENA2400-AC2, ENA2400-DC, 1670,
EAPIR-8, ECPIR-P, ECPIR-3P, EBMDR-8, EAPFX-1, EAPFX-1-V2, EAPFX-6, EAPFX-6-V2, EAPII-1, EAPII-6,
AVC Source Device, IP Speaker, TKIS-2, TKIE-2, IP-LCM, TA-10.
VSFX 1.2.3.7 Firmware for ICX-500 PSC
AlphaSys Firmware 13.0.3.16 Firmware for the ESC1 (Primary System Controller/AMC-IP board) alpha-sys_13.0.3.16.apkg, bsp_32.2.3.6.apkg
VS-EMT Exigo Management Tools EMT-1.7.3.2 Configuration tool, installed on a Windows PC
VS-DEVICE-MIB 202203070000Z SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools


New Feature

EPB-499 Exigo Controller updated to use ICX-500 as PSC

Exigo Controller ESC1 updated to use ICX-500 as Primary System Controller (PSC). Current PSC named AMC-IP shall not be installed at same time.

When using the ICX-500 as PSC this is mounted next to the ESC1. The ICX-500 may either be installed in a 1HU shelf for ICX-500 or mounting bracket for ICX-500. The ICX-500 will be interconnected with the ESC1 via Ethernet cable. From ICX-500 Eth1 connects to ESC1 Eth2. AB systems shall not mix type of PSC in the two Exigo Controllers present. In Exigo Management Tool (EMT) no differences will appear regardless of type of PSC used.

Important: ICX-500 works as the Primary System Controller (PSC) in an Exigo Controller (ESC1) from firmware version vsfx-1.2.3.7.

Enhancements and Fixed Issues

MTN-3989 EMT works when pushing ack all on single systems

In monitoring, the ack all button was causing EMT to crash. This is now solved.

MTN-3988 A failing LET can now be reported as a fault

Before the failing LET would always be reported as a warning independent on what was selected in EMT. This has now been fixed.

MTN-3968 EX panels V2 no longer give fault message: "ETH1 is disconnected"

EX panels do not have Ethernet ports so there is no Ethernet monitoring

MTN-3965 Backup amplifier will check for PSC connectivity

Backup amplifier will ping PSC(s) before taking over any amplifier to make sure that it has connectivity to at least one PSC (Primary System Controller).

MTN-3960 Update of settings on the main web page are now properly applied when saved

When changes are being saved on the main settings' web page, they will be applied and the device will automatically reboot. Earlier you were offered the options to reboot or returning back, which could cause erratic behaviour.

MTN-3945 Enabling configuration option for SLM and LET monitoring at the same time

SLM and LET monitoring can now be enabled on amplifiers except ENA2-AC2.

MTN-3844 X-IGO SIP Header Issue fixed

Fixed an issue that caused the controller to reset if an X-IGO SIP header was used from an external integration while a call was active.

MTN-3807 Removed Channel 2 from configuration view when in bridge mode

In bridge mode (one channel mode) audio Channel 2 is not be visible in view for ENA2X00-AC2 amplifiers anymore.

MTN-3806 Speech sound no longer lost on A/B system takeover

When making configuration changes on GUI, the device gets into a state where speech sound gets lost if A-system (ESC1) loses connection.

MTN-3755 AVC source now has same volume handling as IP Speaker

Previously it had same volume handling as Amplifier

MTN-3582 Authorization required to send EMT changes to PSC

Earlier it was possible in some cases to send changes from EMT to PSC without authorization. This is now fixed.

MTN-3580 Channel shutdown is always reported as fault

Channel shutdown severity warning will not be affected by line fault severity settings, it will always be reported as fault.

MTN-2911 Zone selection - deselect after timeout issue fixed

Configuration with <Enable Timeout> for deselecting zone selection is now working

Known Issues

None